C-26 C60 Breaker Protection System GE Multilin
C.6 ACSI CONFORMANCE APPENDIX C
C
c6: shall declare support for at least one (BRCB or URCB)
c7: shall declare support for at least one (QueryLogByTime or QueryLogAfter)
c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)
c9: shall declare support if TP association is available
c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage)
S44 SetGsCBValues TP O Yes
TRANSMISSION OF SAMPLED VALUE MODEL (SVC) (CLAUSE 19)
MULTICAST SVC
S45 SendMSVMessage MC c10
S46 GetMSVCBValues TP O
S47 SetMSVCBValues TP O
UNICAST SVC
S48 SendUSVMessage MC c10
S49 GetUSVCBValues TP O
S50 SetUSVCBValues TP O
CONTROL (CLAUSE 20)
S51 Select O Yes
S52 SelectWithValue TP O
S53 Cancel TP O Yes
S54 Operate TP M Yes
S55 Command-Termination TP O
S56 TimeActivated-Operate TP O
FILE TRANSFER (CLAUSE 23)
S57 GetFile TP M Yes
S58 SetFile TP O
S59 DeleteFile TP O
S60 GetFileAttributeValues TP M Yes
TIME (CLAUSE 5.5)
T1 Time resolution of internal clock
(nearest negative power of 2 in
seconds)
20
T2 Time accuracy of internal clock
SNTP, IRIG-B
T3 Supported TimeStamp resolution
(nearest value of 2
–n
in seconds,
according to 6.1.2.9.3.2)
20
SERVICES AA: TP/MC SERVER/