EasyManuals Logo

GE C60 User Manual

GE C60
682 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #637 background imageLoading...
Page #637 background image
GE Multilin C60 Breaker Protection System D-5
APPENDIX D D.1 IEC 60870-5-103
D
<251> Write entry aborted
Selection of standard information numbers in control direction
System functions in control direction
INF Semantics
<0> Initiation of general interrogation
<0> Time synchronization
General commands in control direction
INF Semantics
<16> Auto-recloser on/off
<17> Teleprotection on/off
<18> Protection on/off
<19> LED reset
<23> Activate characteristic 1
<24> Activate characteristic 2
<25> Activate characteristic 3
<26> Activate characteristic 4
Generic functions in control direction
INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> General interrogation of generic data
<248> Write entry
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry abort
Basic application functions
Test mode
Blocking of monitor direction
Disturbance data
Generic services
Private data
Miscellaneous
MEASURAND MAX MVAL = TIMES RATED VALUE
1,2 OR 2,4
Current L
1

Current L
2

Current L
3

Voltage L
1-E

Voltage L
2-E
