modications reserved 3 User manual ML Series 350-1000 VA UPS 1.0 (GB)
1 - INTRODUCTION
2 - INSTALLATION
1.1 Introduction
The GE (General Electric) Digital Energy™ ML Series UPS, an uninterruptible power supply, protects your
equipment from all forms of power interference, including complete power failures.
1.2 Safety Rules
CAUTION:• RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The appliance
outlets may be electrically live, even when the UPS is disconnected from the mains.
The UPS contains potentially hazardous voltages. Do not open the UPS, there are no •
user serviceable parts inside.
Apart from battery replacement on the ML 350/500/700 models, all maintenance •
and service work should be performed by qualied service personnel.
Always isolate the UPS from the mains during battery replacement. •
1.3 Transport / Storage
No liability can be accepted for any transport damage when the equipment is shipped in non-•
original packaging.
Before storing, charge the batteries for at least 24 hours.•
Store the UPS in a dry location, storage temperature must be within -20 +45 °C. If the unit is • stored
for a period exceeding 3 months, optimal battery lifetime is obtained if the storage temperature
does not exceed 25°C. Be sure that the UPS is switched off, and that no cable is connected to the
interface port.
If the unit is stored for a period exceeding 3 months, the batteries must be recharged periodically. •
Connect the unit to a wall outlet for a period of approx. 48 hours, minimum every 3 months.
The shipping box contains a Digital Energy™ ML Series UPS, a power cord, a computer interface cable, a
CD ROM and this manual. After unpacking, inspect the UPS for damage. If you nd any damage please
immediately notify the carrier and place of purchase.
IMPORTANT:
Before making any connection and switching on the Digital Energy™ ML Series UPS, please check the
following conditions:
your mains supply is 220 - 240 Volts and 50 Hz, and •
the total power demand of the connected equipment does not exceed the rated output power of •
the UPS (indicated on the rear panel).
2.1 Installation Rules
The UPS is intended to be used in normal domestic and ofce situations.
Protect the UPS, according to the wiring rules, with a 16A D-type fuse.
The UPS must be powered from a single phase grounded wall outlet. Do not use extension
cords.
Avoid locations that are excessively humid, near water, near heat sources or in direct
sunlight.
The ambient temperature should not exceed 40 °C. Optimal battery lifetime is obtained if the
ambient temperature does not exceed 30°C.
It is important that ventilation air can move freely around and through the unit. Do not block
the air vents.
Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.
The UPS output can be used only for electronic loads such as computers and
telecommunications equipment.
Be careful when connecting laser printers: be sure that the demanded power does not
exceed the capacity of the UPS.

Other manuals for GE Digital Energy

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Digital Energy and is the answer not in the manual?

GE Digital Energy Specifications

ML Series model 350

Power IconPower
voltage amperes350 VA
watts210 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage150 Vac
input frequency50 Hz
typical no-load power consumption12 W
Battery IconBattery
nominal voltage12 Vdc
number x capacity of batteries1x5 Ah
recharge current0.5 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight6.5 kg
dimensions150x110x300 mm

ML Series model 500

Power IconPower
voltage amperes500 VA
watts300 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage150 Vac
input frequency50 Hz
typical no-load power consumption12 W
Battery IconBattery
nominal voltage12 Vdc
number x capacity of batteries1x7 Ah
recharge current0.7 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight7.5 kg
dimensions150x110x300 mm

ML Series model 700

Power IconPower
voltage amperes700 VA
watts420 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage150 Vac
input frequency50 Hz
typical no-load power consumption27 W
Battery IconBattery
nominal voltage24 Vdc
number x capacity of batteries2x5 Ah
recharge current0.5 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight11 kg
dimensions150x110x420 mm

ML Series model 1000

Power IconPower
voltage amperes1000 VA
watts600 W
ac input voltage220 - 240 Vac
maximum ac input voltage350 Vac
minimum start-up ac voltage170 Vac
input frequency50 Hz
typical no-load power consumption27 W
Battery IconBattery
nominal voltage24 Vdc
number x capacity of batteries2x7 Ah
recharge current0.7 A
battery recharge time for 80% capacity3 hours
Weight and Dimensions IconWeight and Dimensions
weight13 kg
dimensions150x110x450 mm