EasyManua.ls Logo

GE L30

GE L30
698 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-226 L30 Line Current Differential System GE Multilin
5.7 CONTROL ELEMENTS 5 SETTINGS
5
Figure 5–98: AUTORECLOSURE SCHEME LOGIC (Sheet 2 of 2)
SHOT COUNTER
FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND
To
Sheet 1
Shot Count = MAX
ACTUAL VALUE
FLEXLOGIC OPERAND
Shot cnt = 4
AR1 SHOT CNT = 4
AR
1 SHOT CNT = 2
AR
1 SHOT CNT = 3
AR
1 SHOT CNT = 1
AR
1 SHOT CNT = 0
Increment
shot
counter
Shot cnt = 2
Shot cnt = 1
Shot cnt = 0
Reset shot
counter
Shot cnt = 3
AUTORECLOSE 1
SHOT COUNT: 0(1,2,3,4)
AR
1 CLOSE
AND
AND
AND
AND
AND
AND
AND
AND
100 ms
AND
OR
OR
OR
OR
OR
OR
OR
OR
SETTING
SETTING
SETTING
SETTING
SETTING
AR1 RESET TIME:
AR1 MAX NUMBER
OF SHOTS:
AR1 REDUCE MAX TO 1:
AR1 REDUCE MAX TO 2:
AR1 REDUCE MAX TO 3:
MAX = 1
Off = 0
Off = 0
Off = 0
MAX = 2
MAX = 3
MAX = 4
Close
Bkr is Closed
AR Initiate
LO
Reset from LO
To
Sheet 1
R
S
Latch
O
827082A7.CDR

Table of Contents

Related product manuals