GE Multilin L30 Line Current Differential System 5-227
5 SETTINGS 5.7 CONTROL ELEMENTS
5
Figure 5–99: SINGLE SHOT AUTORECLOSING SEQUENCE - PERMANENT FAULT
BREAKER
STATUS
BKR CLOSED
FAULT
OCCURS
TRIP
COMMAND
FAULT DURATION FAULT DURATION
CONTACTS
SEPARATE
OPENING TIME CLOSING TIME PROT TIME OPENING TIMEPROT TIME
ARC
EXTINGUISHES
ARC
EXTINGUISHES
CLOSE
COMMAND
CLOSED COMMAND BKR CLOSED AR INITIATE
AR GOES TO
LOCKOUT:
SHOT COUNT=MAX
RESET FROM LOCKOUT
AR ENABLED
LOCKOUTRIP
INCOMPL. SEQ. TIMING
RESET TIMER IS TIMING
INCOMPLETE SEQUENCE IS TIMING
DEAD TIME
RECLOSE IN PROGRESS
CONTACTS
CLOSE
TRIP
COMMAND
CONTACTS
SEPARATE
BKR OPEN
AR ENABLED
AUTO RECLOSE
AR INITIATE BKR OPEN
827802A2.CDR