Page #539 background image
GE Multilin L30 Line Current Differential System B-29
APPENDIX B B.4 MEMORY MAPPING
B
Passwords (Read/Write Setting)
400A Setting Password Setting 0 to 4294967295 --- 1 F202 (none)
Passwords (Read/Write)
4014 Command Password Entry 0 to 4294967295 --- 1 F202 (none)
401E Setting Password Entry 0 to 4294967295 --- 1 F202 (none)
Passwords (Read Only)
4028 Command Password Status 0 to 1 --- 1 F102 0 (Disabled)
4029 Setting Password Status 0 to 1 --- 1 F102 0 (Disabled)
Passwords (Read/Write Setting)
402A Command Password Access Timeout 5 to 480 min 1 F001 5
402B Setting Password Access Timeout 5 to 480 min 1 F001 30
402C Invalid Password Attempts (before lockout) 2 to 5 --- 1 F001 3
402D Password Lockout Duration 5 to 60 min 1 F001 5
Passwords (Read/Write)
402E Password Access Events 0 to 1 --- 1 F102 0 (Disabled)
Passwords (Read/Write Setting)
402F Local Setting Auth 1 to 4294967295 --- 1 F300 1
4031 Remote Setting Auth 0 to 4294967295 --- 1 F300 1
4033 Access Auth Timeout 5 to 480 min 1 F001 30
User Display Invoke (Read/Write Setting)
4040 Invoke and Scroll Through User Display Menu Operand 0 to 4294967295 --- 1 F300 0
LED Test (Read/Write Setting)
4048 LED Test Function 0 to 1 --- 1 F102 0 (Disabled)
4049 LED Test Control 0 to 4294967295 --- 1 F300 0
Preferences (Read/Write Setting)
404F Language 0 to 5 --- 1 F531 0 (English)
4050 Flash Message Time 0.5 to 10 s 0.1 F001 10
4051 Default Message Timeout 10 to 900 s 1 F001 300
4052 Default Message Intensity 0 to 3 --- 1 F101 0 (25%)
4053 Screen Saver Feature 0 to 1 --- 1 F102 0 (Disabled)
4054 Screen Saver Wait Time 1 to 65535 min 1 F001 30
4055 Current Cutoff Level 0.002 to 0.02 pu 0.001 F001 20
4056 Voltage Cutoff Level 0.1 to 1 V 0.1 F001 10
87L Channel Status (Read Only)
4059 Channel 1 Local Loopback Status 0 to 2 --- 1 F134 2 (n/a)
405A Channel 1 Loop Delay 0 to 200 ms 0.1 F001 0
405B Channel 1 Number of Lost Packets 0 to 65535 --- 1 F001 0
405C Channel 1 Remote Loopback Status 0 to 2 --- 1 F134 2 (n/a)
405D Channel 1 Status 0 to 2 --- 1 F134 1 (OK)
405E Channel 2 Local Loopback Status 0 to 2 --- 1 F134 2 (n/a)
405F Channel 2 Loop Delay 0 to 200 ms 0.1 F001 0
4060 Channel 2 Number of Lost Packets 0 to 65535 --- 1 F001 0
4061 Channel 2 Remote Loopback Status 0 to 2 --- 1 F134 2 (n/a)
4062 Channel 2 Status 0 to 2 --- 1 F134 2 (n/a)
4063 Channel PFLL Status 0 to 2 --- 1 F134 1 (OK)
4064 87L Network Status 0 to 2 --- 1 F134 2 (n/a)
87L Channel Status (Read/Write Command)
4065 Channel Status Clear 0 to 1 --- 1 F126 0 (No)
87L Power System (Read/Write Setting)
4068 Block GPS Time Reference 0 to 4294967295 --- 1 F300 0
406A Channel Asymmetry Compensation 0 to 4294967295 --- 1 F300 0
406C Charging Current Compensation 0 to 1 --- 1 F102 0 (Disabled)
406D Local Relay ID 0 to 255 --- 1 F001 0
406E Maximum Channel Asymmetry 0 to 10 ms 0.1 F001 15
Table B–10: MODBUS MEMORY MAP (Sheet 21 of 63)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT