28
- At this stage, select the appropriate setting (Note, the presently stored setting has an equals sign before it. Upon selection, this
changes as illustrated):
Press and the M-PRO will display
- And then, modify the settings in order to save it in the M-PRO as follows (Note, after modifying the setting, an equals precedes the
stored value):
Press and hold Press and the M-PRO will display
S/C Curve
= C03, 69ms @ 6Iset
Fixed S/C Crnt
= 8xI_SET 3200A
Fixed S/C Time
= 1.0s
Fixed S/C Time
1.0s
Select
Down Fixed S/C Time
0.9s
Down
Fixed S/C Time
0.8s
Select
Down
Fixed S/C Time
= 0.8s