34
Connections for M-PRO 40
Location Terminal Function
PAMM A1
PAMM A2
OUTPUT 4, normally open volt free contact: Operates when the REF (or SEF) element trips
the ACB. This is used to trip an upstream HV breaker.
PAMM A3
PAMM A4
OUTPUT 3, normally open volt free contact: Used to control shunt trip to open the ACB via
serial link.
PAMM A5
PAMM A6
OUTPUT 2, normally open volt free contact: Load monitoring output will indicate that pre-trip
warn or load shedding is active.
PAMM A7
PAMM A8
OUTPUT 1, normally open volt free contact: Used to control closing coil, facilitating closure
of ACB via serial link.
PAMM A9 Input 4
PAMM A10 Input 3
PAMM A11 Input 2
PAMM A12 Input 1
PAMM A13 Input common
PAMM A14 Remote Rogowski coil – positive
PAMM A15 Remote Rogowski coil – negative
PAMM A16 Host serial link – screen connection
PAMM A17 Host serial link – M-PRO Tx positive
PAMM A18 Host serial link – M-PRO Tx negative
PAMM A19 Host serial link – M-PRO Rx positive
PAMM A20 Host serial link – M-PRO Rx negative
LT ‘B’ block B3
LT ‘B’ block B4
Earth leg CT input – non polarised
LT ‘B’ block B5 Auxiliary power supply input – positive
LT ‘B’ block B6 Auxiliary power supply input – negative
Connections for M-PRO 30
Location Terminal Function
PAMM A1
PAMM A2
OUTPUT 4, normally open volt free contact: Operates when the REF (or SEF) element trips
the ACB. This is used to trip an upstream HV breaker.
PAMM A3
PAMM A4
OUTPUT 3, normally open volt free contact: Operates when M-Pro has opened the ACB
due to a trip condition.
PAMM A5
PAMM A6
OUTPUT 2, normally open volt free contact: Load monitoring output operates if pre-trip
alarm or load shedding limits are exceeded.
PAMM A7
PAMM A8
OUTPUT 1, normally closed volt free contact, opens under the following conditions:
Microprocessor malfunction, primary contact maintenance alarm or a digital input is active.
PAMM A9 Input 4
PAMM A10 Input 3
PAMM A11 Input 2
PAMM A12 Input 1
PAMM A13 Input common
PAMM A14 Remote Rogowski coil – positive
PAMM A15 Remote Rogowski coil – negative
LT ‘B’ block B3
LT ‘B’ block B4
Earth leg CT input – non polarised
LT ‘B’ block B5 Auxiliary power supply input – positive
LT ‘B’ block B6 Auxiliary power supply input – negative
Connections for M-PRO 20
Location Terminal Function
PAMM A14 Remote Rogowski coil – positive
PAMM A15 Remote Rogowski coil – negative
LT ‘B’ block B5 Auxiliary power supply input – positive
LT ‘B’ block B6 Auxiliary power supply input – negative
Connections for M-PRO 17
Location Terminal Function
LT ‘A’ block A8 Remote Rogowski coil – positive
LT ‘A’ block A9 Remote Rogowski coil – negative
LT ‘B’ block B5 Auxiliary power supply input - positive
LT ‘B’ block B6 Auxiliary power supply input - negative