8 3 SERIES RETROFIT – INSTRUCTION MANUAL
MIG AND MIG II RELAYS CHAPTER 1: OVERVIEW
The following table describes MIG II P options, and the equivalent 350 and 345 options and
order codes. In some cases the 350/345 options have changed from those available for
MIG II relays, so read the descriptions carefully.
Metering &
Monitoring
Metering
Event Recording
Metering
Event Recording
Metering
Event Recording
Metering
Event Recording
Oscillography 8 samples/cycle
maximum length 24
cycles
8 samples/cycle
maximum length 24
cycles
up to 32 samples per cycle
(user-selectable)
maximum length 192 cycles
up to 32 samples per cycle
(user-selectable)
maximum length 192 cycles
Communications Serial (RS232, RS485)
protocols: Modbus RTU
Serial (RS232, RS485)
protocols: Modbus RTU
USB
Serial (RS485) protocols:
Modbus RTU, DNP 3.0, IEC
60870-5-103
Ethernet protocols: Modbus
TCP/IP, DNP 3.0, IEC 60870-5-
104, IEC 61850 GOOSE, IEC
61850, OPC-UA
USB
Serial (RS485) protocols:
Modbus RTU, DNP 3.0, IEC
60870-5-103
Ethernet protocols: Modbus
TCP/IP, DNP 3.0, IEC 60870-5-
104, IEC 61850 GOOSE, IEC
61850, OPC-UA
Hardware 2 digital outputs
6 relay outputs
Configurable I/O
Configurable Logic
2 fixed LEDs
4 configurable LEDs
2 digital inputs
6 digital outputs
Configurable I/O
Configurable Logic
2 fixed LEDs
4 configurable LEDs
10 inputs
7 outputs (2 Form A, 5 Form C)
Configurable I/O
Configurable Logic
10 LEDs (non-programmable
LEDs)
12 LEDs (programmable LEDs)
10 inputs
7 outputs (2 Form A, 5 Form C)
Configurable I/O
Configurable Logic
10 LEDs (non-programmable
LEDs)
12 LEDs (programmable LEDs)
1. For additional features, refer to the 350 Instruction Manual.
2. For additional features, refer to the 345 Instruction Manual.
Feature MIG MIG II P
350
1
345
2
Feature MIG order code options MIG II P order code options 350/345 order code options
Application n/a MIGII-P-A11E00HI00
P: Generator Protection Elements
350EP0G0HE-M-NNSNNN
M: Advanced configuration: User
selectable 49, 50P(2), 50G/SG(2),
50N(2), 51P(1), 51G/SG(1), 51N(1),
51_2 or 46(1), 50_2 (1) or 46(1), I1/
I2(46BC)
345EP0G0HE-M-NNSNNN
M: Advanced configuration: 87T,
87T-50, 51P(2), 51N(2), 51G(2),
50P(2), 50G(2), 50N(2), 49P, 46 (51_2/
50_2)(2), 86, 50BF(2), 87G/RGF(2)
Curves MIGP-A-11E000F00C
A: ANSI Curves
I: IEC Curves
MIGIIP-A-11E00HI00
A: ANSI Curves
I: IEC Curves
All 350 and 345 relays come with
ANSI, IEC, and IAC curves standard.
Phase CT Range MIGPA-1-1E000F00C
1: Phase CT = 1 A (0.1 - 2.4 A)
5: Phase CT = 5 A (0.5 - 12 A)
MIFIIPA-1-1E00HI00
0: Phase CT = 1/5 A
1: Phase CT = 1 A
5: Phase CT = 5 A
3xxE-P0-G0HEMNNSNNN
P0: P0 user selectable 1/5 A three-
phase current inputs
Ground CT
Range
MIGPA1-1-E000F00C
1: Ground CT In = 1 A (0.1 - 2.4 A)
5: Ground CT In = 5 A (0.5 - 12 A)
N: Sensitive Ground CT In = 1 A
(0.005 - 0.12 A)
MIGIIPA1-1-E00HI00
1: Ground CT In = 1 A (0.1 - 2.4 A)
5: Ground CT In = 5 A (0.5 - 12 A)
N: Sensitive Ground (0.005 - 0.12 A)
3xxEP0-G0-HEMNNSNNN
G0: user selectable 1/5 A Ground
current input (0.02 - 20 × CT)
S0: user selectable 1/5 A Sensitive
Ground current input (0.002 - 3 × CT)