3 SERIES RETROFIT – INSTRUCTION MANUAL 23
3 Series Retrofit
Chapter 2: Converting Settings
Files
GE
Grid Solutions
Conver ting Setting s Files
Before any mechanical or electrical changes are made, the settings file from the Multilin
MII relay in use must be backed up. The existing settings file can then be converted to a
3
Series settings file. All converted settings and new settings (set to default values) must be
carefully reviewed before the file is uploaded to the new 3
Series relay.
Note
Settings file conversion is currently available for converting most MIF II and MIV II relay
settings files to EnerVista 3 Series Setup software version 2.3x files.
Table 2–1: File conversion support
for 3
Series release 2.3x
MII models FW versions
MIFP V2.14
MIFIIP V301
V401
V402
V403
V404
MIFIIP V502
V503
V504
V505
V506
V507
All MIV II models V310
V401
V402
V403
V404
V405