C-14 F650 Digital Bay Controller GEK-113000T
C.1 FACTORY DEFAULT SETTINGS APPENDIX C
C
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Block from off-line Blk Time After Close 0.00 0.01 s [0.00 : 900.00]
Directional Angle for stage 1 Dir Power Angle 1 0.00 0.01 Deg [0.00 : 359.99]
Pickup level for stage 1 Stage 1 Tap 10.00 0.01MW [-10000.00 : 10000.00]
Trip time for stage 1 Stage 1 Time 60.00 0.01 s [0.00 : 900.00]
Directional Angle for stage 2 Dir Power Angle 2 0.00 1 Deg [0.00 : 359.99]
Pickup level for stage 2 Stage 2 Tap 20.00 0.01MW [-10000.00 : 10000.00]
Trip time for stage 2 Stage 2 Time 60.00 0.01 s [0.00 : 900.00]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Setting Grouping Permission Function DISABLED N/A [DISABLED – ENABLED]
Active Group Active Group GROUP 1 N/A
[GROUP 1 – GROUP 2 –
GROUP 3]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup level Pickup Level 49.50 0.01 Hz [20.00 : 65.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Minimum voltage threshold Minimum Voltage 30 1 V [30 : 300]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]