C-18 F650 Digital Bay Controller GEK-113000T
C.1 FACTORY DEFAULT SETTINGS APPENDIX C
C
SETPOINT > CONTROL ELEMENTS >POWER
WATT GND FLT HIGH 1> WATT GND FLT HIGH 2 > WATT GND FLT HIGH 3
WATT GND FLT LOW 1> WATT GND FLT LOW 2 > WATT GND FLT LOW 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED-ENABLED]
Supervision minimum voltage Voltage Pickup Level 2 0.01 V [2.00 : 70.00]
Source of operating current. Current selection IN N/A [IN-IG]
Pickup Level for Overcurrent OC Pickup Level 0,005 0.001A [0.005 : 0.400]
Pickup Delay for Overcurrent OC Pickup Delay 0,2 0.01 s [0.00 : 600.00]
Pickup Level for operating Power Power Pickup 0,01 0.01 W [0.01 : 4.50]
Max torque angle MTA 0 1 Deg [0 : 360]
Pickup Delay for Operating Power Power Pickup Delay 0,2 0.01 s [0.00 : 600.00]
Curve shape Curve DEFINITE TIME N/A [DEFINITE TIME -
INVERSE TIME - USER
CURVE A - USER CURVE
B - USER CURVE C -
USER CURVE D]
Multiplier Multiplier 1 0.01 s [0.02 : 2.00]
Snapshot event generation Snapshot Event DISABLED N/A [DISABLED-ENABLED]