GEK-113000T F650 Digital Bay Controller 2-7
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
2.4.1.2 GROUND TIME OVERCURRENT (51G)
2.4.1.3 NEUTRAL TIME OVERCURRENT (51N)
Current Input Phasor (without harmonics) or RMS
Rated current For connection to 1 or 5 A CTs.
Pickup level 0.05 to 160.00 A in steps of 0.01 A
Dropout level 97% to 98% of the pickup level
Level Accuracy
Values at nominal frequency:
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
Curve Shapes IEEE extremely / very / moderately inverse
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / moderately inverse
ANSI extremely / very / normally / moderately inverse
I
2
t
Definite time
Rectifier curve
FlexCurve A/B/C/D user curve
Curve Multiplier (Time Dial) 0.00 to 900.00 s in steps of 0.01 s
Reset type Instantaneous or time delayed according to IEEE
Timing accuracy Operate at > 1.03 times the pickup ±3% of operate time or
50 ms. (whichever is greater)
Saturation Level 48 times the pickup level
Snapshot Events Selectable by setting
Current Input Fundamental Phasor (without harmonics)
Pickup level 0.05 to 160.00 A in steps of 0.01 A
Dropout level 97% to 98% of the pickup level
Level Accuracy
Values at nominal frequency:
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
Curve Shapes IEEE extremely / very / moderately inverse
IEC A/B/C/long-time inverse/short time inverse curve
IAC extremely / very / moderately inverse
ANSI extremely / very / normally / moderately inverse
I
2
t
Definite time
Rectifier curve
FlexCurve A/B/C/D user curve
Curve Multiplier (Time Dial) 0.00 to 900.00 s in steps of 0.01 s
Reset type Instantaneous or time delayed according to IEEE
Timing accuracy Operate at > 1.03 times the pickup ±3% of operate time or
50 ms. (whichever is greater)
Saturation Level 48 times the pickup level
Snapshot Events Selectable by setting

Table of Contents

Other manuals for GE Multilin F650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin F650 and is the answer not in the manual?

GE Multilin F650 Specifications

General IconGeneral
BrandGE
ModelMultilin F650
CategoryController
LanguageEnglish

Related product manuals