44x/EN ST/Hb6 
 
-48  MiCOM P40 Agile 
 
 
Menu Text  Default Setting 
Setting Range 
Step Size 
Min.  Max. 
MEASUREMENT SETUP 
Fault Location  Distance  Distance / Ohm / % of Line 
The calculated fault location can be displayed using one of several options selected using 
this setting. 
3.7   “Communications” column 
The communications settings are available in the menu ‘Communications’ column and are 
displayed when the “Comms Settings” setting (“Configuration” column) = “visible”. 
3.7.1  Communications settings for courier protocol 
Menu Text  Default Setting 
Setting Range 
Step Size 
Min.  Max. 
COMMUNICATIONS 
RP1 Protocol  Courier 
Indicates the communications protocol that will be used on the rear communications port. 
RP1 Address   255  7  34  1 
This cell sets the unique address for the relay such that only one relay is accessed by 
master station software. 
RP1 Inactiv Timer  15 mins.  1 mins.  30 mins.  1 min. 
This cell controls how long the relay will wait without receiving any messages on the rear 
port before it reverts to its default state, including resetting any password access that was 
enabled. 
Physical Link  Copper  Copper, (RS485), Fibre optic 
This cell defines whether an electrical connection (“Copper” or “RS485” according to 
software version) or fiber optic connection is being used for communication between the 
master station and relay. The optional fiber optic communications board will be required if 
‘Fiber optic’ is to be selected. 
RP1 Status  Data 
This cell indicates the status of the rear communication board. 
RP1 Port Config.  KBus  KBus or EIA(RS)485 
This cell defines whether an electrical KBus or EIA(RS)485 is being used for communication 
between the master station and relay. 
RP1 Comms. Mode  IEC60870 FT1.2  
IEC60870 FT1.2 or 10-Bit No Parity 
The choice is either IEC60870 FT1.2 for normal operation with 11-bit modems, or 10-bit no 
parity. 
RP1 Baud Rate  19200 bits/s  9600 bits/s, 19200 bits/s or 38400 bits/s 
This cell controls the communication speed between relay and master station. It is important 
that both relay and master station are set at the same speed setting.