Modifications reserved Page 26/79
OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
`Home\Meter
INVERTER
f 60 Hz
L1 277 V
L2 277 V
L3 277 V
T +25° C
SYNCHRONIZED
Inverter data screen
f The output frequency of the Inverter.
L1
L2 Three-phase output voltage PHASE/NEUTRAL.
L3
T The temperature of the inverter bridge.
The synchronization status of the inverter with respect to
utility (SYNCHRONIZED / NOT SYNCHRONIZED).
`Home\Meter
SYSTEM LOAD
L1 :
277 V 180.0 A 50 %
L2 :
277 V 144.0 A 40 %
L3 :
277 V 108.0 A 30 %
LOAD ON INVERTER
Load on phases screen 1
… V Output voltage PHASE/NEUTRAL for each phase.
… A The output current as RMS values (for RPA: total
value of Parallel System).
… % The output load as percentage (for RPA: with
respect to the rated power of Parallel System).
The source of the power supplied to the load:
- DETOUR ON (Q2 close) - LOAD ON INVERTER
- Q1 OPEN
- LOAD ON BYPASS
- LOAD OFF
- LOAD ON BYPASS (eBoost)
- ON BATTERY
`Home\Meter
SYSTEM LOAD
L1 :
44.8 kW 49.8 kVA PF +/-0.90
L2 :
35.8 kW 39.8 kVA PF +/-0.90
L3 :
26.9 kW 29.9 kVA PF +/-0.90
LOAD ON INVERTER
Load on phases screen 2
… kW The load active power (kW) (for RPA: total value of
Parallel System).
… kVA The load apparent power (kVA) (for RPA: total
value of Parallel System).
… PF The load power factor:
+ for inductive loads (lagging power factor).
- for capacitive loads (leading power factor).
The source of the power supplied to the load:
- DETOUR ON (Q2 close) - LOAD ON INVERTER
- Q1 OPEN
- LOAD ON BYPASS
- LOAD OFF
- LOAD ON BYPASS (eBoost)
- ON BATTERY
`Home\Meter
MODULE LOAD
Total kVA 120 kVA
Percentage 40%
LOAD ON INVERTER
Module load screen
Total kVA
The load level in kVA (for RPA: only this unit).
Percentage
The load level as a percentage of the nominal rated load
(for RPA: only this unit).
The source of the power supplied to the load:
- DETOUR ON (Q2 close)
- LOAD ON INVERTER
- Q1 OPEN - LOAD ON BYPASS
- LOAD OFF
- LOAD ON BYPASS (eBoost)
- ON BATTERY