OPM_SGS_USM_M22_M30_2US_V010.doc User Manual SG Series 225 & 300 UL S2
Code Message Meaning
4699
BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
No Utility Rectifier or Bypass.
Battery not fully charged.
Load is below 10% or above 80%.
Test is postponed for 1 week.
4763
REMOTE CONTROL ON
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only Local Panel.
1 = Only Remote Control.
2 = Both.
4764
REMOTE CONTROL OFF
Inverter cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only Local Panel.
1 = Only Remote Control.
2 = Both.