Fn_10 : Operation Control
= 0 : Keypad
= 1 : External terminal TM2
Note:
When Fn_10=1 (external operation control), emergency stop on the keypad is enabled.
When Fn_10=1, please refer to the descriptions of F_23/24, in order to avoid the damage
to the human and the machine.
Fn_11 : Frequency control
= 0 : Frequency instruction is setup by keypad
= 1 : Frequency instruction is setup by VR or analog signal
on TM2 ( 0 up to 10V / 0-20mA )
= 2 : Frequency instruction is setup by VR or analog signal
on TM2 ( 4-20mA )
Note 1:
When Jog frequency or Sp1 frequency is switched on,
the frequency is setup by Sp1 speed, the
▲▼
buttons on the keypad is disabled. Original setting
will be restored after Sp1 connection is OFF.
Note 2:
During the contact closure of the jog function,
the keypad control remains in a sleep state until the
jog contact connection is re-opened.
Time
Hz
F_10=1
or =0
F_09=10Hz
F_19=1
F_08=30Hz
F_20=2
ON OFF
OFF
ON OFF
ON
OFF
OFF ON
OFF