35
F_28: Direct start
= 0 : Direct start enable when remote Run command on
= 1 : Direct start disable when remote Run command
on drives with CPU version from 2.1
(check function F_29)
When F_28 = 1 and control mode is remote control (F_10 = 1), the inverter can not start if RUN switch is
ON when power is engaged, must be turned the RUN switch OFF and turned ON again, then inverter
can start.
Fn_29: software (program) version
Fn_30: Fault trace
1. Fault trace : indicate the sequence of the occurrence of malfunctions by the location of decimal
point. x.xx indicate a recently happened malfunction. xx.x indicate the last malfunction that
happened. xxx. indicated the earliest malfunction in the record.
2. After entering the Fn_30 function, the x.xx record will be displayed first. After that, press button
can read out xx.x xxx. x.xx ,,, consecutively.
3. After entering Fn_30 function, if the RESET button is pressed, all three malfunction record will be
cleared. Indication display
-.--, --.-, and ---.
4. When the content of malfunction memory indicate O.CC, indicate the latest malfunction code is
OC-C and so on.