2-22 VersaMax Modules, Power Supplies and CarriersUser Manual GFK-1504N
2
Wiring for a Box-Style I/O Carrier or Spring-Style I/O Carrier
(IC200CHS002, IC200CHS005)
B
A
H
G
F
8
2
4
6
B
C
7
D
3
Field Wiring
Terminals
Each terminal on a Box-Style or Spring-Style I/O Carrier accommodates one
solid or stranded AWG #14 (avg. 2.1mm
2
cross section) to AWG #22 (avg.
0.36mm
2
cross section) wire, or two wires up to AWG #18 (avg. 0.86mm
2
cross
section). Use copper wire rated for 90 degrees C. When inserting two wires in
the same position, the wires must be the same size and type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8
Amps per each power and ground, and a voltage range of up to 264 V AC.
Voltage transients up to 300 V AC will not damage the carrier.
For a Box-Style I/O Carrier, recommended terminal torque is 0.37 to 0.45 ft-lbs.
The label provided with the module can be folded and inserted in the module’s
transparent door.
Terminal Numbering for a Box-Style or Spring-Style I/O Carrier
A1
A2
A3
A4
A5
A6
A7
A8
A9
A11
A12
A13
A14
A15
A16
A17
A18
A10
B2
B3
B4
B5
B6
B7
B8
B9
B11
B12
B13
B14
B15
B16
B17
B18
B10
B1