8 | Commissioning
Makesurethatthesuctionandpressurelineshut-offvalvesareopen.
Withthecompressorswitchedoff,addtheliquidrefrigerantdirectlytothecondenserorreceiver,
breakingthevacuum.
Iftherefrigerantneedstoppingupafterstartingthecompressor,itcanbetoppedupinvapour
formonthesuctionside,or,takingsuitableprecautions,alsoinliquidformattheinlettothe
evaporator.
8.5 Refrigerantcharge
CAUTION Wearpersonalprotectiveclothingsuchasgogglesandprotective
gloves!
ATTENTION Avoidoverllingthesystemwithrefrigerant!
Toavoidshiftsinconcentration,zeotropicrefrigerant blendsmust
alwaysonlybelledinto therefrigeratingplantinliquidform.
Donotpourliquidcoolantthroughthesuctionlinevalveon
thecompressor.
Itisnotpermissibletomixadditiveswiththeoiland
refrigerant.
8.6 Start-up
Checkthatthesafetyandprotectiondevices(pressureswitch,motorprotection,electrical
contactprotectionmeasures,etc.)areallfunctioningproperly.
Switchonthecompressorandallowtorunforaminimumof10min.
Checktheoillevel by:Theoilmustbevisibleinthesightglass.
WARNING Ensurethatbothshut-offvalvesareopenbeforestartingthe
compressor!
ATTENTION Iflargerquantitiesofoilhavetobetoppedup,thereisariskof
oilhammereffects.
Ifthisisthecasechecktheoilreturn!