9 | Maintenance
9.5 Decommissioning
Closetheshut-offvalvesonthecompressor.Draintherefrigerant(itmustnotbedischargedintothe
environment)anddisposeofitaccordingtotheregulations.Whenthecompressorisdepressurised,
undothefasteningscrewsoftheshut-offvalves.Removethecompressorusinganappropriatehoist.
Disposeoftheoilinsideinaccordancewiththeapplicablenationalregulations.
9.4 Extractfromthelubricantstable
Theoiltypelledasstandardinthefactoryismarkedonthenameplate . Thisoiltypeshouldbe
used as a preference.Alternativesarestatedintheextractfromourlubricantstablebelow.
Donotmixoilswitheachother,useonlyonetypeofoil.
Refrigerants Bockstandardoiltypes
Recommendedalternatives
HFC
(e.g.R134a,R407C,
R404A)
FuchsRenisoTritonSE55
FuchsRenisoTritonSEZ32
Esso/MobilEALArctic46
SunocoSunisoSL46
TexacoCapellaHFC55
HFO(e.g.R1234yf,
R1234ze,R455A,
R454C))
FuchsRenisoTritonSE55
FuchsRenisoC85E(fromt
O
>15°C)
---
HCFC
(e.g.R22) FuchsRenisoSP46
FuchsRenisoSP32
BPEnergolLPT46
SunocoSuniso3,5GS
TexacoCapellaWF46
HC(e.g.R290) FuchsSynth68
CPI1516-68
9.6 Additionalinformationwhenusingammablerefrigerants
WARNING •Duringmaintenanceandrepair,itmustbenotedthathydrocarbon
and synthetic HFO refrigerants residues may dissolve in the
oil. Therefore, electrical tests must not be conducted while oil
remainsinthecompressor.
•If the compressor is to be removed from the system for
maintenance or repair, the remaining refrigerant must be
suctioned out and the compressor evacuated. The compressor
must then be filled with nitrogen (max. 0.5 bar) and sealed
gas-tight.