EasyManua.ls Logo

GEA Bock HGZ Series - 4 Description of Functions

GEA Bock HGZ Series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
D
GB
F
E
09726-09.2013-DGbF
Therefrigerantsuctionedoutoftheevaporator(21)iscompressedbythe4cylindersoftheLPstage
(2)tointermediatepressureMP.Afterthat,thesuperheatedrefrigerantowsthroughtheintermediate
pressurechamber(3),whereitiscooledbytheliquidsubcoolersystemtoreducethedischargeend
temperature.The refrigerant then ows through the intermediate pressure line (4) to the electric
motorofthecompressorfortocoolthemotor.Afterthis,therefrigerantissuctionedinbythetwoHP
cylinders(5)andcompressedtothenalpressure.
Liquidsubcoolersystem
Theliquidsubcoolersystemconsistsofthecomponents
-liquidsubcooler(plateheatexchanger)(6)
-expansionvalve(7)
-sightglasses(8,9)
-solenoidvalve(10)
-lterdrier(11)
Aftertherefrigerantreciever(16),theliquidlinewillbesplittedintotwolines:
Line A leads through the liquid subcooler (6) and the subcooled refrigerant ows to the
evaporator (21).Through Line B refrigerant isexpandingthroughtheexpansion valve (7) into the
liquidsubcooler(6)inordertosubcooltherefrigerantoflineAandthroughtheintermediatepressure
line(MP)tocoolthesuperheatedrefrigerant,whichiscompressedfromlowpressuretointermediate
pressurechamber(3).
4| Description of functions

Related product manuals