5.2 Installationoftheliquidsubcoolersystem (standardversion)
Separatelyenclosedcomponents:
Liquidsubcooler
Reinjectionvalve
Solenoidvalve
Filterdrier
2 sightglasses
Screw-insleeve,solderadapterandseals
Pleasecheckforcompletenessofpartsbeforebeginninginstallation.
INFO! Observe manufacturer‘s instructions!
Assembly:
INFO! The points listed here represent general guidelines and information
onhowtopipeandconnectthesubcoolerunit.Toperformthiswork
technicalknowledgeandskillaswellasproofofahard-soldering
testcerticateinaccordancewithDINEN13133isrequired.
Pipe connections:
Forconnections,seedimensiondiagram Chapter 10.
Systemdesign,pipingandnecessarysupportpointsfortheindividualcomponents
mustbecarefullyplannedandcarriedout.
Properlyinsulateliquidsubcooleragainstcondensationandheatingandtherelated
lossofperformance.
Forrigidityreasons,theuseofstainlesssteelpipeswithawallof1mmispreferred.
Thepipesmustbefreeoftensionduringandaftersolderingtopreventpossible
breakslateron.
INFO! Useonly suitablehard solder and ux.Solder under an inert gas
atmosphere when copper components are to be soldered! The
accompanying expansion valve is designed and adjusted for the
compressor and the listed refrigerant (sensor charge, nozzle).
OnlyuseexpansionvalvesapprovedandsuppliedbyBock!
INFO! The intermediate pressure line and intermediate pressure chamber
are fully insulated at the factory. To mount the expansion valve,
cuttheinsulationasshowninthemarkedareainFig.17,page16.
Correctsensor placementismarkedbyanunpaintedareaonthe
pipe.
1
2
3
4
5
6
1
2
3
4
5
6
ATTENTION! To avoidvibrationcracksinthesubcoolersystem,theindividual
components must be mounted directly to the compressor or
installed as a decoupled unit!
5| Compressor assembly
Fig.18