6| Electrical connection
ThecompressorandthetriggerunitMP10areoperationalwhentheH3LED(green)lights.
6.6 Function test of the trigger unit MP 10
Pos
Procedure
LED H1 LED H2 LED H3
red red green
1
Interrupt power supply (L1 or S1) OFF OFF OFF
Releasethemotortemperaturesensorconnection(1or2)
Releasethehotgastemperaturesensor(ifinstalled)(3or4)
2
Restore the power supply (L1 or S1) ON
Functioncheckofmotortemperaturesensor:operational ON
Functioncheckofhotgastemperaturesensor:operational ON
3
Interrupt power supply again (L1 or S1) OFF OFF OFF
Reconnectterminals1or2and/or3or4
4
Restore the power supply (L1 or S1): OFF OFF ON
MP10isoperationalagain
Beforestart-up,troubleshootingormakingchangestothecontrolpowercircuit,checkthefunctionality
ofthetriggerunit: