6| Electrical connection
6.4 Electronic trigger unit MP 10
The compressor motor is tted with cold conductor temperature sensors (PTC) connected to the
electronictriggerunitMP10intheterminalbox.ReadinesstooperateissignalledbytheH3LED
(green)afterthepowersupplyisapplied.Inthecaseofexcesstemperatureinthemotorwinding,the
unitswitchesoffthecompressorandtheH1LEDlightsred.
Thehotgassideofthecompressorcanalsobeprotectedagainstovertemperatureusingathermal
protectionthermostat(accessory).TheH2LED(red)isprovidedfortheprotectionfunction.
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.
INFO!
The device has a reclosure preventing feature. After eliminating the
fault, the device is quit by interrupting the mainspower with the
externalalarmresetswitchS1(seemain-linewiringdiagram,chap-
ter5.3).ThereclosurepreventingfeatureisunlockedandLEDsH1or
H2 go off again.
Terminalbox
Fig.29
ATTENTION!
Terminals 1 - 6 on the trigger
unit MP 10 and terminals PTC
1 and PTC 2 on the compres-
sor terminal board must not
come into contact with mains
voltage. This would destroy the
trigger unit and PTC sensors.
The supply voltage at L1-N
(+/-forDC24Vversion)must
be identical to the voltage at
terminals11,12,14and43.
6.5 Connection of the trigger unit MP 10
INFO! Connect the trigger unit MP10 in accordance with the circuit
diagram. Protect the trigger unit with a delayed-action fuse (F) of
max.4A.Inordertoguaranteetheprotectionfunction,installthe
triggerunitastherstelementinthecontrolpowercircuit.
Temperaturemonitoringconnections:
Motorwinding: Terminals 1 - 2
Thermalprotectionthermostat: Terminals 3 - 4
Restartprevention: Terminals 5 - 6