Generac
®
Power Systems, Inc. 13
Section 3 — Operation
PM-GC
Low Battery Voltage (1/100ths volt) Warning Alarm Units Comment
Setpoint
Shutdown N
Dialout N
Common alarm Y
Alarm log N
Sensor failure detection N
Shutdown on sensor failure N
Delay 60 seconds seconds
Active Hold off
Hysteresis 200 1/100ths volt
High Battery voltage (1/100ths volt)
Setpoint
Shutdown N
Dialout N
Common alarm Y
Alarm log N
Sensor failure detection N
Shutdown on sensor failure N
Delay 0 seconds
Active Hold off
Hysteresis 200 1/100ths volt
High Gen. Voltage A,B,C (Volts RMS)
Setpoint
Shutdown N
Dialout N
Common alarm Y
Alarm log Y
Sensor failure detection N
Shutdown on sensor failure N
Delay 0.5 seconds seconds
Active Hold off
Hysteresis 10 Vrms
Low Gen. Voltage A,B,C (Volts RMS)
Setpoint
Shutdown N
Dialout N
Common alarm Y
Alarm log Y
Sensor failure detection N
Shutdown on sensor failure N
Delay 0.5 seconds seconds
Active Hold off
Hysteresis 10 Vrms
Over Speed (rpm)
Setpoint
Shutdown Y
Dialout Y
Common alarm Y
Alarm log Y
Sensor failure detection Y
Shutdown on sensor failure Y
Delay 0.1 seconds seconds
Active Immediate
Hysteresis 20 RPM