What to do if the Generac Power Systems Controller LCD panel shows no screen?
D
Deborah WatsonAug 7, 2025
If the LCD panel on your Generac Power Systems Controller isn't displaying anything, try the following: First, check the fuse block for a blown fuse that supplies the controller assembly. Next, ensure the battery is connected and has at least 6V. Then, verify that the connectors are properly seated in the Base Board. Finally, press the screen to ensure it is not in Sleep Mode.
J
Julie JonesAug 13, 2025
Why doesn't the engine crank on my Generac Power Systems Power Zone Pro Controller when in MANUAL?
Y
ywilliamsAug 13, 2025
If the engine on your Generac Power Systems Controller fails to crank when the keyswitch is in the MANUAL position, consider these potential solutions: First, make sure the Emergency Stop button is disengaged (pulled out). Second, check the Emergency Stop wiring to ensure it's properly connected. Third, verify that the keyswitch is correctly wired. Lastly, check the touchscreen display for any active alarm conditions and acknowledge them.
V
vlangAug 18, 2025
How to fix a blinking Comm indicator on Generac Power Systems Controller LCD screen?
S
Samantha WongAug 18, 2025
If the Comm indicator on your Generac Power Systems Controller LCD screen is blinking, here are a few things to check: First, make sure you're using a shielded twisted pair cable. Second, verify that the shield of the RS-485 cable is grounded at one end. Third, try reversing the Data(+) and Data(-) wires at one connector.
B
Bradley RiveraAug 26, 2025
What to do if the Engine ECU doesn't communicate with Generac Power Systems Power Zone Pro?
M
Michael HughesAug 26, 2025
If the Engine ECU is not communicating with the Power Zone Pro, verify the cable connection is a shielded twisted pair. Also, verify the shield is grounded at one end of the cable.
S
Shawn WatsonAug 31, 2025
Why can't I hear the audio alarm on my Generac Power Systems Power Zone Pro Controller?
N
Nicholas GriffinAug 31, 2025
If you cannot hear the audio alarm when an alarm condition exists on your Generac Power Systems Controller, verify the horn is wired properly.