14 Generac
®
Power Systems, Inc.
Section 3 — Operation
PM-GC
Under Speed (rpm) Warning Alarm Units Comment
Setpoint
Shutdown N
Dialout N
Common alarm Y
Alarm log N
Sensor failure detection Y
Shutdown on sensor failure Y
Delay 0.5 seconds seconds
Active Hold off
Hysteresis 20 RPM
Over Frequency (1/10ths Hz)
Setpoint 1/10ths Hz
Shutdown Y
Dialout Y
Common alarm Y
Alarm log Y
Sensor failure detection N
Shutdown on sensor failure N
Delay 0.2 seconds seconds
Active Hold off
Hysteresis 5 1/10ths Hz
Under Frequency (1/10ths Hz)
Setpoint 1/10ths Hz
Shutdown N
Dialout N
Common alarm Y
Alarm log N
Sensor failure detection N
Shutdown on sensor failure N
Delay 0.5 seconds seconds
Active Hold off
Hysteresis 5 1/10ths Hz
High Fuel level (%) Warning Alarm Units Disabled unless probe fitted
Setpoint %
Shutdown N
Dialout N
Common alarm N
Alarm log N
Sensor failure detection N
Shutdown on sensor failure N
Delay 2 seconds seconds
Active Always
Hysteresis 2 %\
Low Fuel level (%) Warning Alarm Units Disabled unless probe fitted
Setpoint %
Shutdown N
Dialout N
Common alarm N
Alarm log N
Sensor failure detection N
Shutdown on sensor failure N
Delay 2 seconds seconds
Active Always
Hysteresis 2 %