RENTAL SERIES
ELECTRICAL GENERATOR
ALARMS:
The following chart describes each alarm:
NUMBER SYMBOL DESCRIPTION
Z
Fuel level below minimum.
Y
Low battery voltage.
X
Emergency stop.
W
Engine overspeed.
V
Low oil pressure.
U
High engine temperature.
T
If engine does not start after 3 attempts, the unit will be stopped and this icon will be
displayed.
S
Low engine speed.
H
Hz
Alternator frequency beyond established limits.
Hz
V
Alternator voltage beyond established limits.
A
A
If it is detected that the generator’s output current exceeds the established value for
an extended period of time, this warning will be displayed.
I
f the cutoff point for overcurrent is exceeded by 10% for one hour, the unit will be
stopped.
N
ote: If the established limits defined as warning or stop are exceeded, the module will display the corresponding alarm. None of these
will be shown if not detected by the system.