LRR 1-50, LRR 1-51 - USA - Installation & Operating Manual - 850702-01
Action against high-frequency interference
Further information
High-frequency interference can be caused by out-of-phase switching operations. If such in-
terference occurs and results in sporadic failure, we recommend taking the following action to
suppress interference:
Provide inductive loads with RC combinations as specified by the manufacturer.
Route the connecting cable to the conductivity electrode or conductivity transmitter sepa-
rately from power lines.
Increase the distance from sources of interference.
Check that the shield is correctly connected. Check the shield of items of equipment with the
aid of the Installation & Operating Manuals. If equalizing currents are likely (outdoor installa-
tions), connect the shield on one side only.
Suppress HF interference using hinged-shell ferrite rings.