6. Operation
Work mode3: Backup Mode
This mode can coexist with Self-use or Feed in priority and is only suitable for lithium
battery.In this mode,part of the battery capacity is reserved for the Backup load in case
of power failure.The Backup SOC needs to be set to define the capacity to retain the
battery .The “Allow Grid Charging” is recommended to be turned on.
Backup Mode
Backup Mode Switch
Reserver SOC
80%
Work mode4: Off-Grid Mode
This mode is only used for pure off-grid and is not recommended for normal storage
systems.Note that if this mode is enabled in the grid-connected state,the working logic
of the machine will be confused and the “Off-grid” will be displayed.
Off-Grid Mode
Off-grid Mode Switch
Off-grid Overdischarge SOC
30%
33
>
>