PRoDUcT SPeciFicATionS
PRoDUcT SPeciFicATionS
4 www.goodmanmfg.com SS-GPC13H
SPeciFicATionS (conT.)
GPC13
42H41AC
GPC13
48H41BA
GPC13
49H41AB
GPC13
60H41BA
GPC13
60H41BC

Total BTU/h 41,000 45,500 45,500 57,500 57,500
Sensible BTU/h 31,600 34,700 34,700 43,000 43,000
SEER / EER 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0 13.0 / 11.0
Decibels 78 80 80 80 80
AHRI # 4635460 4635472 4635461 4635473 4635462

Type PSC PSC PSC EEM EEM
Wheel (D x W) 10 x 8 10 x 8 10 x 8 11 x 8 11 x 8
Nominal Cooling CFM 1,410 1,585 1,585 1,850 1,850
RLA / LRA 2.87 / 4.9 2.87 / 4.9 2.87 / 4.9 5.8 / 8.0 5.8 / 8.0
No. of Speeds 3 3 3 3 3
Horsepower - RPM ½ - 1,005 ½ - 1,075 ½ - 1,005 ¾ - 1,250 ¾ - 1,250

Face Area (²) 6.2 6.2 6.2 7.0 7.0
Rows Deep / Fins per Inch 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14
Filter Size (“) (2) 20x20x1 (2) 20x20x1 (2) 20x20x1 (2) 20x25x1 (2) 20x25x1
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.) 88 110 80 160 93

Horsepower - RPM ¼ - 1,075 ¼ - 1,075 ¼ - 1,075 ¼ - 1,075 ¼ - 1,075
RLA / LRA 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9
Fan Diameter/ # Fan Blades 22 / 4 22 / 4 22 / 4 22 / 4 22 / 4
Face Area (²) 16 19.1 16 19.1 19.5
Rows Deep / Fins per Inch 1 / 28 1 / 21 1 / 28 2 / 16 1 / 28

Quanty 1 1 1 1 1
Type Scroll Scroll Scroll Scroll Scroll
Stage Single Single Single Single Single
Compressor RLA / LRA 17.9 / 112 19.9 / 109 19.9 / 109 26.4 / 134 26.4 / 134

Voltage-Phase 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Indoor Blower FLA 2.87 2.87 2.87 5.8 5.8
Outdoor Fan RLA 1.4 1.4 1.4 1.4 1.4
Total Unit Amps 22.2 24.17 24.17 33.6 33.6
Min. Circuit Ampacity¹ 26.6 29.2 29.2 40.2 40.2
Max. Overcurrent Protecon (amps)² 40 45 45 60 60
 370 400 400 400 400
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.