EasyManuals Logo

Goodman M Series User Manual

Goodman M Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image


SYMPTOM
POSSIBLE CAUSE REMEDY
High head - low suction
a. Restriction in liquid line or flowrator
a. Remove or replace with proper size flowrator.
High head - high or normal suction
a. Dirty condenser coil
b. Overcharged
c. Condenser fan not running
a. Clean coil
b. Correct System charge
c. Repair or Replace
Low head - high suction
a. Incorrect flowrator
b. Defective compressor valves
c. Flowrator not seating properly
a. Replace with correct flowrator
b. Replace compressor
c. Check for debris under flowrator or deformed
flowrator. Remove debris or replace flowrator.
Unit will not run
a. Power off or loose electrical connection
b. Thermostat out of calibration set too high
c. Defective contactor
d. Blown fuses or tripped breaker
e. Transformer defective
f. High or low pressure control open
(Optional)
g. Compressor overload contacts open
a. Check for unit voltage at contactor in unit
b. Reset
c. Check for 24 volts at contactor coil replace if
contacts are open
d. Replace fuse or reset breaker Check wiring -
replace transformer
f. Reset high pressure control or check unit charge
High pressure control opens at 610 psig
Low pressure control opens at 22 psig
g. Replace compressor
NOTE: Wait at least 2 hours for overload to
reset
Condenser fan runs,
compressor doesn't
a. Loose connection
b. Compressor stuck, grounded or open
winding open internal overload
c. Low voltage connection
d. Capacitor weak, open, or shorted
a. Check for unit voltage at compressor check
& tighten all connections
b. Wait at least 2 hours for overload to reset If still
open, replace the compressor.
c. At compressor terminals, voltage must be within
10 % of nameplate volts when unit is operating
d. Check capacitor. If defective, replace.
Low suction - cool compressor
Iced evaporator coil
a. Low indoor airflow
a. Increase speed of blower or reduce restriction
- replace air filters
Compressor short cycles
a. Defective overload protector
b. Unit cycling on low pressure control
c. High pressure switch cuts out
a. Replace - check for correct voltage
b. Check refrigerant charge and / or airflow
c. Check airflow (Indoor & outdoor)
Registers sweat
a. Low airflow
a. Increase speed of blower or reduce
restriction replace air filters
High suction pressure
a. Excessive load
b. Defective compressor
c. Reversing valve not seating properly.
a. Recheck load calculation
b. Replace
c. Replace
Insufficient cooling
a. Improperly sized unit
b. Improper airflow
c. Incorrect refrigerant charge.
d. Incorrect voltage
a. Recalculate load
b. Check - should be approximately 400 CFM per ton
c. Charge per procedure attached to unit
service panel
d. At compressor terminals, voltage must be within
10% of nameplate volts when unit is
operating
Evaporator coil freezing or frosting
a. Low airflow
b. Low refrigerant charge
c. Operating unit in cooling mode below
65°F outdoor temperature
a. Check - should be approximately 400 CFM per
ton, dirty air filters, all duct outlets open
b. Properly charge unit
c. Install or check low ambient control, should be
open below 65°F outdoor temperature

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodman M Series and is the answer not in the manual?

Goodman M Series Specifications

General IconGeneral
BrandGoodman
ModelM Series
CategoryHeat Pump
LanguageEnglish

Related product manuals