AIRFLOW
43
Adjustments Through DIP Switch Combinations
7 - 8
DIP Switch Settings
for Single & Two-Stage Thermostats
MODEL
SWITCH
3
SWITCH
4
THERMOSTAT
N/A ON Si ngle Stage
N/A OFF Two-Stage
APC15/H16**
CFM
SWITCH
7
SWITCH
8
Plus10% ON OFF
Normal OFF OFF
Minus10% OFF ON
MODEL
SPEED
TAP
SWITCH
5
SWITCH
6
COOLING/HP
CFM
A Off Off
816
(F)
B On Off 850
C Off On 907
D On On 955
A Off Off
940
(F)
B On Off 987
C Off On 1034
D On On 1,073
A Off Off
954
(F )
B On Off 1067
C Off On 1179
D On On 1273
A Off Off 1222
B On Off 1298
C Off On
1327
(F)
D On On 1395
A Off Off
1394
(F)
B On Off 1499
C Off On 1605
D On On 1708
A Off Off
1500
(F)
B On Off 1600
C Off On 1700
D On On 1800
(F)
Factory Setting
APC1548
APH1648
APC1560
APC1524
APH1624
APC1530
APH1630
APC1536
APH1636
APC1542
APH1642
MODEL
SPEED
TAP
SWITCH
1
SWITCH
2
ELECTRIC
HEAT (CFM)
A Off Off
816
(F)
B On Off 850
C Off On 907
D On On 955
A Off Off
940
(F)
B On Off 987
C Off On 1034
D On On 1,073
A Off Off
954
(F)
B On Off 1067
C Off On 1179
D On On 1273
A Off Off 1222
B On Off 1298
C Off On
1327
(F)
D On On 1395
A Off Off
1394
(F)
B On Off 1499
C Off On 1605
D On On 1708
A Off Off
1500
(F)
B On Off 1600
C Off On 1700
D On On 1800
(F)
Factory Setting
APC1542
APH1642
APC1548
APH1648
APC1560
APC1524
APH1624
APC1530
APH1630
APC1536
APH1636

Table of Contents