60
10 Technical Parameters
User Manual V1.0-2022-01-17
Inrush Current(peak and
duration) (A/us)
30/50 30/50 30/50 50/50
Nominal Output Current (A) 11.6 14.5 21.7 28.9
Maximum output overcurrent
protection(A)
38.4 38.4 88.9 88.9
Output Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion <3%
Eciency
Max. Eciency 98.4% 98.4% 98.4% 98.4%
European Eciency 97.5% 97.5% 97.5% 97.5%
Protection
DC Insulation Resistance
Detection
Integrated
Residual Current Monitoring Unit Integrated
DC Reverse Polarity Protection Integrated
Anti-islanding Protection Integrated
AC Overcurrent Protection Integrated
AC Short Circuit Protection Integrated
AC Overvoltage Protection Integrated
DC Switch Integrated
DC Surge Arrester Type II
AC Surge Arrester Type III
DC Arc Fault Circuit Interrupter Optional
Emergency Power O Optional
Remote Shutdown Optional
Active anti-islanding method Integrated (AFD)
General Data
Operating Temperature Range
(℃)
-30~60 (60 °C for outdoor unconditioned with solar eects.)
Relative Humidity 0~100%
Max. Operating Altitude (m) ≤4000
Cooling Method Natural Convection Smart Fan Cooling
Display LED, LCD, APP(Wi-Fi)
Communication RS485,Wi-Fi / LAN
Communication Protocol SunSpec Modbus
Weight (Kg) 20.5 20.5 26 26