EasyManua.ls Logo

Gossen MetraWatt METRAHit 28C light - Read-Out a Periodic Ramp - RAMP Function

Gossen MetraWatt METRAHit 28C light
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 GOSSEN METRAWATT GMBH
8.2 Read-Out a Periodic Ramp – RAMP Function
Ramp-type signals can be used to test dynamic performance
of devices under test, or entire measuring circuits. An exam-
ple would be control loop performance with a setpoint speci-
fied via the analog setpoint input at the controller. The instru-
ment can be used to replace costly hardware and software
for the set-up of long-term test bays with cyclical time
sequences.
Parameters for the ramps depicted below include:
The following functions can be adjusted as output quanti-
ties:
voltage U, current sink I Sink, current source I Source,
resistance R or temperature temp.
•A lower (Start) and an upper (End) range limit can be
selected for each output quantity. For standard signals
these are always 0 10 V and 0/4 20 mA, and are
otherwise values from within the entire range.
Rise time t1 and decline time t3 are
adjustable from 0 seconds 60 minutes.
Dwell time t2 at the upper and lower range limits is
adjustable from 0 seconds 60 minutes.
There are 2 ramp sequences:
– Once only: t1, t2, t3
– Repetitive: t1, t2, t3, t2, t1, t2, t3,
Examples of Ramp Sequences:
Example of a Periodic Ramp Sequence
Manually Controlled Ramp Sequences
After configuring all parameters in accordance with the menu
flowchart on page 15, rising or declining ramps can be trig-
gered with the " and the # keys.
The relationship between the output signal and each of the
key operations is depicted with the help of the following
example.
Example of a Manually Controlled Ramp Sequence
Ramp parameters
: Output quantity: U (0 15 V range),
Start =2V, End = 10 V, t1 = 5 s, t2 = 8 s, t3 = 5 s,
repeat = Yes (yes for periodic ramp)
Key
1 The sequence is started by pressing the key when ramp
start is displayed (see Menu Flowchart on page 16).
2 Stop the declining ramp within decline time t3 with the "
or the # key.
3 Start a rising ramp within remaining decline time t3 with
the " key.
4 Stop the ramp sequence with the " or the # key.
5 Start a declining ramp with the # key, remaining dwell
time t2 is deleted.
6 Stop the ramp sequence by simultaneously pressing and
holding the " and the # keys (2 audible acoustic signals
must be generated).
Start
End
t1
t2
t3
t2
Output
t
2V
10 V
t1 t2 t3
LCD:
t3 t2
t1
➀➁
t1 up t2 run t3 dn t3 hld t3 up t3 run t3 hld t1 dn
stop cont.
stop
cont.
U
[V]
+
"
#
#
"
#"#
"

Related product manuals