765041982 Rev. 000 28
"Compressor": Styreparametre for Kompressor
Parameter Description Setting range Default
C
Compressor
C1
Hysteresis
1=0/-1, 2=+1/-1,
3=+1/-2
4=+2/-2, 5=+2/-3,
6=+3/-3
2
C2
Upper temperature limit +25 … -35 °C +10
C3
Lower temperature limit +25 … -35 °C -30
C4
Pause time for compressor restart 0 … 30 min.
5
C5
Condenser sensor configuration
0 = no sensor;
1 = 1 sensor (C);
2 = 2 sensors (C, D)
2
C6
Compressor stop at door opening 0 … 15 min. 5
"Fan", Styreparametre for fordamperblæser
Parameter Description Setting range Default
F
Fan (evaporator fan)
F1
Evaporator fan start after
defrosting
0 … -10 °C -1
F2
Running- /pause time ratio for
evaporator fan: Pause
0 … 10 min. 4
F3
Running- /pause time ratio for
evaporator fan: Running time
0 … 99 sek. 60
