765041982 Rev. 000 29
"Defrost", Afrimningsparameter
Parameter Description Setting range Default
d
"Defrost": Afrimning
d1 No. of defrosts / 24 hours 1 … 8 4
d2
Defrost temperature limit 0 til 30 °C 12
d3
(”manual”) initial defrosting 0 = On / 1 = Off 0
d4
Maximum defrost time 10 … 60 min. 30
d5
Defrost mode
1 = automatic
(depending on setting "d7")
2 = air
3 = electric (defrost heater)
3
d6
Drip time 0 …10 min. 2.
d7
Temperature limit at
automatic defrosting
at "d5" = 1:
+2 … +25°C
+4
d8
Evaporator monitoring, if
exceeding, forced defrosting
follows
-5 .. -50 °C -40
d9
Defrosting by termination of
"PCL", "HCL", "SCL"
0 =On ... 1 =Off 1