32
Grant Vortex Indoor/Utility, System and Boiler House Oil Boilers
Fig. 21 - Boiler flue connector
Refer to Section 4.11 and 4.12 and Fig. 12. for the size,
type and position of the connections.
The Flow and Return pipework can be routed to either
side of the boiler, dependant on the type and direction
of the flue system used.
For condensate disposal pipework refer to Section 5.
Pipe entry/exit holes in case (Indoor/Utility, System)
All models except the 155/200 and 200/240 have holes
to enable the pipework to exit the boiler casing. On the
50/70 and 50/90 models these holes are pre-cut knock-
outs located at the rear of both side panels and on the
90/120 and 120/155 models these pre-cut holes are in
the removable flue outlet cover plates.
Push out the 'knock-out' from the required holes,
taking care not to distort the side panel.
If access will be restricted, make any connections to
the boiler before placing it in its final position.
If using a balanced flue system - Install the balanced flue
system before connecting the heating system pipework to
the boiler. Once the flue system is fitted then complete the
water connections and fill the heating system.
If using a conventional flue system - Complete the
water connections and fill the heating system.
Check all connections for leaks and rectify as necessary.
1. Lift off upper rear casing panel.
2. Remove the insulation from the underside of the
panel (do not discard it). Carefully press out the
pre-cut flue opening in the top panel.
3. The flue dress panel supplied in the literature pack.
Place the dress panel in position on the rear casing
top panel and secure in place.
4. Re-fit the insulation to the panel with the foil
surface facing outwards. With a sharp knife cut
around the edge of the round opening in the dress
plate to leave a round hole through the insulation
for the flue.
5. If the Grant ‘Orange’ flue system is being used –
follow the instructions supplied with the flue kit.
6. Fully screw the length of threaded studding
(provided in the kit) into the nut located in the
centre of the boiler flue outlet.
Make the water connections
6.4
6 - BOILER INSTALLATION
7. Fit the boiler connector (from the CF adaptor kit)
over the threaded studding. Position flange on to
the neoprene gasket around the boiler flue outlet,
ensuring that small spigot on the base of the
connector is located in the hole in the centre of the
neoprene gasket and that end of studding passes
through the hole in the of the spacer bracket. Fit
washer and wing nut provided onto end of threaded
studding and secure connector in position by
tightening down on wing nut – as shown in Fig. 21.
8. Re-fit the rear top casing panel to the boiler –
fitting it over the boiler connector.
9. Fit the flue adaptor (from the adaptor kit) into the
boiler connector. Note lubricate the seal on the
adaptor using the lubricant provided before
attempting to fit the flue adaptor.
10. Fit the first section of flue into the flue adaptor and
secure using the clamp band provided.
11. Assemble the remainder of the flue system as
required, lubricating the seal on each component
before fitting.
Connect a conventional flue
6.5