6.6.15. - Always on
Relay is always switched on.
6.6.16. - Heating circuit
Heat circuit pump is controlled with a xed hysteresis of (+/-1° for setpoint temperature).
30 seconds Switch on and Switch off delay is xed setting to prevent unnecessary switching of the
pump.
RC21 room controller can be used as room temperature sensor.
Settings range: On, Off
6.6.16.1. - Room set day
Room reference temperature in day mode. If this temperature is exceeded at the room
temperature sensor at the set times, the relay is switched off.
Settings range: 10 to 30° C
6.6.16.2. - Room set night
Room reference temperature in night mode. If this temperature is exceeded at the room
temperature sensor at the set times, the relay is switched off.
Settings range: 10 to 30° C
Special functions
Relay functions
6.6.16.3. - Room sensor
This menu determines the sensor for the room temperature.
Settings range: S2 to S7, RC
6.6.16.4. - Periods
Set the desired periods of time when the heat circuit day mode should be active. 3 periods can be
set per day, settings can also be copied to other days. Outside the set times the heating function is
working in night mode.
Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00
6.6.14. - Parallel operation R (X)
The relay is switched on at the same time as the set relay R1 or R2.
Settings range: On, Off, Inverted
6.6.14.1. - Delay
This menu determines how long after the start of R1 or R2 the parallel relay is switched on.
Settings range: 0-120 seconds / Default setting: 30 seconds
6.6.14.2. - Followup time
This menu determines how long after the switch off of R1 or R2 the parallel relay is switched off.
Settings range: 0-120 seconds / Default setting: 30 seconds