7.3 Other Malfunctions and Solutions (No display on LED wire controller)
LED wire controller
no display.
Check cable and circuit
breaker if it is connected
LED wire controller.
displays the actual time.
Heat pump under standby
status
Startup heat pump to run.
LED wire controller
displays the actual
water temperature.
1. Water temperature is
reaching to setting value,
HP under constant
temperature status.
2. Heat pump just starts to
run.
3. Under defrosting.
1. Verify water temperature
setting.
2. Startup heat pump after a
few minutes.
3. LED wire controller should
display "Defrosting".
LED displays actual water
temperature, no error code
displays.
1. Fan NO running.
2. Air ventilation is not
enough.
3. Refrigerant is not
enough.
1. Check the cable
connections between the
motor and fan, if necessary, it
should be replaced.
2. Check the location of heat
pump unit, and eliminate all
obstacles to make good air
ventilation.
3 Replace or repair the heat
pump unit.
Water stains on heat pump
unit.
1. Concreting.
2. Water leakage.
1. No action.
2. Check the titanium heat
exchanger carefully if it is any
defect.
Too much ice
on evaporator
Too much ice on
evaporator.
1. Check the location of heat
pump unit, and eliminate all
obstacles to make good air
ventilation.
2. Replace or repair the heat
pump unit.