45
D Series Modular Air-cooled Scroll Chillers
Service Manual
)LQWXEH+HDW([FKDQJHU
1RWH%HVXUHWRFXWRIIWKHSRZHUVXSSO\DQGUHFRYHUWKHUHIULJHUDQW¿UVWO\
Steps Graphic Representation Instructions
1. Remove
the panel as
shown the
ULJKW¿JXUH
ƹ
Recover refrierant completly.
ƹ
Cut off the power supply.
ƹ
Remove the fan assembly and draw out
the power cord of the fan motor and then
remove the metal sheets outside the
condenser.
Note: remember the wiring sequence of the
fan motor.
2. Unbraze
the inlet/
outlet pipeline
of the heat
H[FKDQJHU
Do not
damage the
¿QVDQGPHWDO
sheets during
unbrazing
Brazing spot
ƹ
Unbraze the pipeline of the condenser.
3. Remove
the frame of
the header
and screws
and bolts
on the heat
H[FKDQJHU
Frame
ƹ
Remove the frame of the header with a
wrench.
ƹ
Remove screws and bolts on the heat
H[FKDQJHU