INSTALLATION
114
The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m).
Thus, the total length is over than 30m, so the air conditioner needs to add refrigerant.
Additional refrigerant charge
Σ the Liquid Pipe Length of Φ6.35×0.022kg/m +Σ the Liquid Pipe Length of Φ9.52×0.054kg/m-1.47(kg)
=(5+5+5+5+5+5)(m)×0.022kg/m+(20+10+10)(m)×0.054kg/m-1.47(kg)
=1.35(kg)
4) Additional refrigerant charge record
Diameter(mm) Total length(m) Additional refrigerant charge(kg)
Φ6.35
Φ9.52
Total
6.11.3 Procedures for adding refrigerant
NO. 1 2 3 4 5
Name Outdoor unit Service port Liquid side stop valve Gas side stop valve
Pressure-vacuum
gauge
NO. 6 7 8 9
Name Hi-knob Lo-knob R410A tank Scale
1) When the liquid and gas stop valves have not been opened, the system is under the vacuum:
Refer to the left of the figure; connect the R410A tank to the system.
Turn on the R410A tank and the Hi-knob; charge the R410A refrigerant into the system from the liquid
side stop valve. The Lo-knob should be closed completely.
Turn off the R410A tank and the Hi-knob immediately, when the adding refrigerant is enough.
Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
2) If the pressure of the system is too high to charge refrigerant, you can do as follow.
Turn on the liquid and gas side stop valves in an anticlockwise direction slowly and completely.
Turn on the power of the air conditioner, and set cooling mode, running more than 0.5h when outside
temperature is higher than 18 DB.
a) Refer to the left of the figure; connect the R410A tank to the system.
b) Turn on the R410A tank and the Lo-knob, charge the R410A refrigerant into the system from the gas
side stop valve. The Hi-knob should be closed completely.
c) Turn off the R410A tank and the Lo-knob immediately, when adding refrigerant is enough.
Turn on the power of the air conditioner, and set heating mode, running more than 0.5h when outside
temperature is lower than 18 DB.
a) Refer to the right of the figure, connect the R410A tank to the system.
b) Turn on the R410A tank and the Hi-knob, charge the R410A refrigerant into the system from service
port. The Lo-knob should be closed completely.