GREE                                                          DC Inverter Multi VRF System II Service Manual 
142 
IDU 
Liquid pipe: 
Total length of each liquid pipe 
Φ9.52˖A+B+C+a=10+105+5+3=23m 
Φ6.35: D+b+c+d=5+3+2+1=11m 
Note: Liquid pipe that is within 20m doesn’t need to be added with refrigerant. 
Therefore, the minimum quantity of additional refrigerant = (23-20)×0.054+11×0.022
˙
0.404kg   
˄2˅Calculate the additional volume of refrigera˄GMV-80WL/C-TǃGMV-100WL/C-Tǃ
GMV-121WL/C-T  ǃGMV-80WL/A-TǃGMV-100WL/A-TǃGMV-121WL/A-TǃGMV-120WL/C-Tǃ
GMV-140WL/C-TǃGMV-160WL/C-TǃGMV-120WL/C-XǃGMV-140WL/C-X,GMV-160WL/C-X˅ 
1)  Refrigerant quantity of outdoor unit before delivery: 
C
 Note: 
ķ The refrigerant amount charged before delivery doesn’t include the amount that needs to be 
added to indoor units and the connection pipeline.
ĸ Length of connection pipe is decided on site. Therefore the amount of additional refrigerant 
shall be decided on site according to the dimension and length of field-installed liquid pipe.   
Ĺ Record the amount of additional refrigerant for convenience of after-sales service. 
2)  Calculation of the amount of additional refrigerant 
Calculation method of the quantity of additional refrigerant (based on liquid pipe) 
Quantity of additional refrigerant = ∑length of liquid pipe ×quantity of additional refrigerant per 
meter+˄quantity of indoor unit -2˅×0.3 
Quantity of additional refrigerant per meter for liquid pipe˄kg/m˅
First confirm that there is no leakage from the system. When compressor is not working, charge 
additional R410a with specific amount to the unit through the filling opening of the liquid pipe valve of the 
outdoor unit. If required amount cannot be quickly filled due to pressure increase of the pipe, then set the 
unit in cooling startup and fill refrigerant from the low pressure check valve of the outdoor unit.