GREE                                                          DC Inverter Multi VRF System II Service Manual 
78 
2.2 Status display table for indicators on main board of outdoor unit   
Definition:  
z  LED1: It displays “00” for hot water mode as for DC Inverter Side Discharge VRF 
z  LED2: It displays “AC” for AC mode, cooling and cooling OFF mode for indoor unit, and displays 
“AH” for heating and heating OFF mode for indoor unit   
z  LED3: It displays on or off status of compressor and malfunction code. It displays “ON” when the 
compressor is operating and “OFF” when the compressor stops operation. When there’s 
malfunction for the unit, it will display corresponding malfunction code; when there’re multiple 
malfunctions, the malfunction codes will be displayed in turn.     
Display code table of outdoor unit is as below:   
Content 
Content 
Content 
E0
Malfunction of outdoor 
unit 
E1
E2
Low-temperature 
protection for dicharge 
E3
E4
Discharge high temperature 
protection for compressor 
EC
Loose protection  for 
discharge temperature 
sensor for compressor 1 
F0
Poor main board of 
outdoor unit 
F1
Malfunction of high 
pressure sensor 
F3
Malfunction of low 
pressure sensor 
F5
Malfunction of discharge 
temperature sensor for 
compressor 1 
FP
Malfunction of 
J0
J1
Overcurrent protection for 
compressor 1 
J7
Air-mixing protection for 
4-way valve 
J8
High pressure ration 
protection of system 
J9
protection of system
JL
b1
Malfunction for outdoor 
ambient temperature 
sensor 
b2
Maflunction of defrosting 
temperature sensor 1 
b3
M
temperature sensor 2
b4
Malfunction of liquid 
temperature sensor for 
subcooler 
b5
Malfunction of gas 
temperature sensor for 
subcooler 
b6
Malfunction for temperature 
sensor of inlet tube of gas 
and liquid separator 
b7
Malfunction for 
temperature sensor of exit 
tube of gas and liquid 
separator (exit tube A) 
b9
Malfunction of gas exit 
temperature sensor for 
heat exchanger 
bH
P0
for compressor 
P1
Driven board of 
compressor works 
abnormally 
P2
Power voltage protection for 
the driven board of 
P3
driven module of 
P4
Driven PFC protection of 
compressor 
P5
Overcurent protection for 
inverter compressor 
P6
Driven IPM module 
protection for compressor 
P7
Malfunction of driven 
temperature sensor for 
compressor 
P8
Overheating protection for 
driven IPM of compressor 
P9
Desynchronizing 
protection for inverter 
compressor 
PH
High voltage protection 
for driven DC bus bar of 
compressor 
PC
Circuit malfunction of driven 
current detection for 
compressor 
PL
Low voltage protection for 
driven DC bus bar of 
compressor 
PE
-
compressor 
PF
charging loop for 
Failure start up for inverter 
compressor 
PP
AC current protection for 
inverter compressor 
Preheat time is not enough 
for compressor 
U2
Capacity code of outdoor 
unit/wrong setting of 
jumper cap 
U4
Insufficient refrigerant 
protection 
Wrong address for the 
driven board of compressor 
U6
Alarm due to abnormal 
valve 
U8
Malfunction of pipeline for 
indoor unit 
Malfunction of pipeline for 
outdoor unit 
UC
Setting for indoor unit and 
oudoor unit is succeeded 
UL
Wrong code-dialing 
during emergency 
UE
Refrigerant-charging is 
invalid 
C0
Communication 
malfunction for indoor unit,