GREE                                                          DC Inverter Multi VRF System II Service Manual 
56 
 
Usage of converter configuring software: 
z  When the converter is working, hold the button ”SET” for 5 sec. Function LED will be flickering, 
indicating that the converter has enter the baud rate setting mode. Then you can use the converter 
configuring software to set the baud rate of converter. Baud rate supported by the converter (baud 
rate of air conditioner’s communication interface matches with the baud rate of USB interface 
automatically): 
Ex-factory defaulted baud rate: (unit: bps) 
AC is connected with 
Baud rate of air conditioner interface 
Baud rate of USB interface
CAN 
20000
/
50000 
self-adaptive 
115200 
HBS 
57600 
38400
 
RS485 
9600 9600 
Baud rate look-up table for RS485 interface (unit: bps) 
RS485 interface
4800 9600 
38400
57600
USB interface 
4800 9600 
38400
57600