GREE                                                          DC Inverter Multi VRF System II Service Manual 
70 
1.2 Debugging of unit   
Debugging procedure for test run, display instruction for indicator on main board of outdoor unit and 
operation method are as below:   
GMV-80WL/A-T  GMV-100WL/A-T GMV-121WL/A-T GMV-80WL/C-T  GMV-100WL/C-T
  GMV-121WL/C-T GMV-120WL/C-T GMV-140WL/C-T GMV-160WL/C-T GMV-120WL/C-X
  GMV-140WL/C-X GMV-160WL/C-X  
GMV-H224WL/A-X GMV-H280WL/A-X GMV-H335WL/A-X GMV-H224WL/A-X
  GMV-H280WL/A-X GMV-H335WL/A-X  
GMV-224WL/C-X     GMV-280WL/C-X     GMV-335WL/C-X 
Stage process instruction for debugging 
Code instruction and operation method 
unit setting 
A
No debugging status for system
 
Press SW7 button on main board for 5s to start 
system debugging. The indicator on main board is 
displayed as shown in the left. 2s later, it will enter 
into next step determination.
 
02_ Address distribution 
Address distribution for the system. 10s later, the 
display is as below: 
No main indoor unit. Display will be kept for 1min. 
Within 1min, set the main i
ndoor unit through 
debugging software. If notset the main indoor unit 
by hand within 1min, the system will automatically 
set the minimum IP address as the main indoor 
unit.
 
The distribution for the system address is finished. 
2s later, 
it will enter into the next step 
determination automatically.
 
03_Quantity 
confirmation of 
outdoor unit 
Cofirmation process of system. 1s later, it will 
enter into the next step automatically.
 
 system. 2s later, it will 
enter into the next step automatically.
 
04_Quantity confirmation of indoor 
unit 
LED3 displays quantity of indoor unit. The quanity 
of indoor unit shall be confirmed by perform. If the 
actural quantity of indoor unit is different from the 
displayed quantity, cut off the power for indoor unit 
and outdoor unit. Check whether the 
communication wire for indoor unit is normal. After 
that, put through the power and start debugging 
from step 01.    If the quantity o
f indoor unit is 
SW7 button on main board to 
confirm it. The display is as below after 
confirmation: