GREE                                                          DC Inverter Multi VRF System II Service Manual 
76 
for the system is -15~8ć. 
Opening angle of 
electrocnic 
expansion valve 
for heating 
●During cooling operation, the electronica expansion valve 
for heating will always be kept at 480PLS;
 
●During heating operation, the ope
ning angle for the 
adjusted electronic expansion valve is 55~480PLS. 
Operation 
frequency for 
compressor 
95HZ 
Operation current 
of compressor 
Current should be no more than 25.0A during normal 
operation for compressor 
IPM module 
temperature for 
compressor 
ć
When ambient temperature is lower than 35ć, temperature 
for IPM module is lower than 80
ć. The maximum 
temperature won’t exceed 95
ć
Operation 
frequenc for fan 
It will adjust the frequency among 0~49HZ for operation 
according to the system pressure 
unit
Ambient 
temperature for 
indoor unit 
ć
 
Entry tube 
temperature for 
indoor heat 
exchanger 
ć
●According to the difference of ambient temperature, the 
entry tube temperature is 1
ć~7ć 
lower than the exit tube 
temperature for the same indoor unit under cooling mode; 
4~9
ć  higher than low pressure. 
●Under heating mode, entry temperature is 10
ć~20ć 
lower than exit tube temperature for the sae indoor unit.
 
Entry tube 
temperature for 
indoor heat 
exchange 
ć
 
angle of 
indoor electrocnic 
expansion valve 
Under cooling mode, the opening angle for indoor electronic 
expansion valve is adjusted among 70~480PLS.
 
Under heating mode, the opening angle for indoor unit is 
adjusted among 40~480PLS. 
Communication 
paraters 
data 
Through debugging software, it detected that the quantity of 
indoor unit is same with the enginerring actural quantity. 
There’s no communication malfunction. 
Drainage syste  —— 
Water can be drained smoothly for indoor unit; Outdoor unit 
can drain water fromo drainage pipe completely.