49 
 
Fig.3.9.12 Two wired controllers control multiple IDU 
When two wired controllers control multiple IDUs, the wired controller can be connected to any 
one IDU, provided that the connected IDU is of the same series. Meanwhile, one and only one of the 
wired controllers must be set as a slave controller. At most 16 IDUs  can be controlled by wired 
controllers and the connected IDUs shall be within a same IDU network. 
No matter when unit is turned on or off, slave controller can be set. 
How to set a slave controller: hold “function”  button on the designated controller for 5s, and 
temperature zone displays C00. Continue holding “function”  button for 5s and setting screen of 
controller parameter will come out. Default temperature zone displays P00. 
Press button or  button to select parameter code P13. Press “mode” button to switch to setup 
of parameter values. Then the parameter value will blink. Press button or button to select code 02. 
And then press “confirm/cancel” to finish setting. 
Press “confirm/cancel” to return to the previous display until you exit from the setup of parameter 
values. 
Below are user’s parameter settings: 
Parameter 
code 
Parameter 
name 
Parameter scope 
Default 
value 
Remark 
P13 
Set up 
address for 
wired 
controller 
01: master wired 
controller 
02: slave wired 
controller 
01 
When 2 wired controllers control one or 
more IDUs, they shall have different 
addresses. Slave wired controller (02) can’t 
set up units’ parameters except its address. 
3.9.7 Other Communication Connection Methods 
For the communication connection among indoor units, between ducted type indoor unit and the 
receiving light board, please refer to the indoor unit manual.