4.4 Parameter Judgment Reference Value for Unit Normal Operation 
Debugging Parameter Reference Value for DC Inverter VRF Unit 
1 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
System 
parameter 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Outdoor 
unit’s 
parameter 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Outdoor ambient 
℃ 
—  — 
2 
Discharge pipe 
temperature of inverter 
℃ 
● When the compressor starts running, the 
normal discharge pipe of cooling or shell 
top temperature is 70~95
℃
, above 10
℃
 
higher than the saturation temperature of 
system high pressure; the normal heating 
temperature is 65~90
℃
, above 10
℃
 
than the saturation temperature of system 
— 
3 
Shell top tube 
temperature of inverter 
℃ 
— 
4 
Discharge pipe 
temperature of inverter 
℃ 
— 
5 
Shell top tube 
temperature of inverter 
℃ 
— 
6 
Temperature of 
defrosting temperature 
sensor   
℃ 
● When the system is running in cooling 
mode, the temperature of defrosting 
temperature sensor is 5~11
℃
 lower than 
system high pressure; 
● When the system is running in heating 
mode, the temperature difference between 
the defrosting temperature sensor and the 
system low pressure is about 2
℃
— 
7  System high pressure 
℃ 
● The normal high pressure value of the 
system is 20
℃
 ~55
℃
. According to the 
change of ambient temperature and the 
change of operating capacity of the 
system, the high pressure value of the 
system is 10
℃
 ~40
℃
 higher than the 
ambient temperature. The higher the 
ambient temperature, the smaller the 
temperature difference;   
● When the unit operating in the cooling 
mode at the ambient temperature of 
25~35
℃
, the system high pressure value is 
44~56
℃
;   
● When the unit operating in the heating 
mode at the ambient temperature of -
5~10
℃
, the system high pressure value is 
℃
— 
8  System low pressure 
℃ 
● When the unit operating in the cooling 
mode at the ambient temperature of 
25~35
℃
, the system low pressure value is 
0~8
℃
; 
● When the unit operating in the heating 
mode at the ambient temperature of -
5~10
℃
, the system low pressure value is -
℃
— 
9 
Opening of electronic 
expansion valve of 
heating   
PLS
● During cooling operation, the electronic 
expansion valve of heating is 3000PLS; 
● During heating operation, the adjustable 
range of the opening of electric expansion 
valve opening is 720~3000PLS.   
—